Motors & Transformers

Low Voltage Motors

FEATURESVALUES/ STANDARDS
Ambient Temperature-10 to +50°C
AltitudeNot exceeding 1000mtrs above mean sea level.
AtmosphereNon corrosive & non hazardous
Relative HumidityUp to 100%
Voltage415V±10% , 3 ph.
Frequency50Hz ±5%
Combined Variation10%
DutyS1 (continuous)

Service factor

1.0

 

FEATURESVALUES/ STANDARDS
StartingDOL for all Or Star delta for frames 100 & above.
Permissible starts/hr2 Hot / 3 Cold / 4 Equally spread
Loading at reduced volts75% Rated volts for 5 minutes
Insulation / temp.riseClass ‘F’/70 deg C
Direction of rotationBi-Directional
No. Of leads3 up to 90 frame & 6 for including and above 100 frame
ConnectionStar up to 90 frame and , Delta including and above 100 frame
Degree of protectionIP55, IP 66 on request.
Method of coolingIC 411
T.box positionTop TB Standard and side TB – optional ( RHS from DE)
Bearing life
40,000 hours for direct drive, 20,000 hours for belt drive
VibrationNormal class as per IS 12075
NoiseAs per IS 12065.
ConstructionFoot, ‘B’ flange, ‘C’ flange, Foot cum ‘B’ flange , Foot cum ‘C’ flange
Frame sizesRavi series 63-315
Mounting arrangementMultiple mounting holes in same body, S/M/L as per standard
Shaft extensionSingle cylindrical extension as per IS 1231
Body materialCI from 63-315 frame
T.box materialNylon Up to 132 frame /sheet metal 160 frame and above
Fan materialPolypropylene up to 225frame/ 250 and above fabricated steel
Accessories
Nil, Thermistor, space heater, winding RTD, BTD on request in select frames.
Paint & shadeStandard Motor
Main body: Shade RAL 1020
Fan cover: Shade 592 of IS 5 International orange
Bearing type and
Greasing facility
Sealed Bearings grease lubricated for life up to 225 frame and open bearings with online greasing facility in 250 and above frames.

 

Rerolling Mill Duty Motor

FEATURESVALUES/ STANDARDS
Ambient Temperature0 to +45°C
AltitudeNot exceeding 1000mtrs above mean sea level.
AtmosphereNon corrosive & non hazardous
Relative HumidityUp to 100%
Voltage415V±10% (Can also be offered upto 650V)
Frequency50Hz. ±5%
Combined VariationAny combination of voltage and frequency

 

FEATURESVALUES/ STANDARDS
StartingStator Rotor Starter/Liquid Rotor Starter
Permissible starts/hr.2 Hot Or 3 Cold or 4 Equally spread
Loading at reduced voltsThese motors are designed to run at 75% of rated supply voltage for a duration of five minutes.
Insulation / temp.riseClass F/F
Temp rise Stator/RotorClass B/F
Direction of rotationBi-directional
No. Of leadsTR 5&6 > ST: 6 and RT: 3 Rest 3 / 3
Degree of protectionIP23
Method of coolingIC01
T.box positionLeft hand side when viewed from non-drive end, reversible assembly at site is not possible.
Terminal box arrangementFor KCW 450 & 500: Stator – 43506201, Rotor – 43521599.
For KCW 560: Stator – 41102205, Rotor – 43506101. Terminal box rotatable through 3600 in steps of 180° (i.e cable entry possible from top or buttom)
Bearing life(90% survival basis)Lithium based grease to “Grade 3” as per IS: 7623 for 4 pole & above motors.
LubricantDirect drives: 40,000 working hours.(Based on 90% survival life)
VibrationNormal class as per IS: 12075.
NoiseAs per IS: 12065.
Shaft extension.Single cylindrical extension as per IS: 1231.
Body materialMild Steel
T.box materialMild Steel
Fan materialMild Steel
Accessories
Refer to Kirloskar Electric engineering department.
Paint & shadeEpoxy “RAL BLUE” to shade plate K-102
Bearing type and
Greasing facility
Antifriction rolling contact (Ball & Roller)
Online greasing facility for all frames

 

Power Distribution Transformers

160 kVA to 2500 kVA, up to 33 kV Class

 

Kirloskar Transformers are designed and tested to the following standards:

The company is capable of manufacturing transformers to any other standards as per customers’/consultants’ requirements.

Scroll to Top